phone Phone
+6281290773137
close
menu

CV. Andalan Prima Sejahtera

sql
Fluke T6-600 Electrical Tester
Fluke T6-600 Electrical Tester
Hover to Zoom

Jual Fluke T6-600 Electrical Tester



Spesifikasi Fluke T6-600 Electrical Tester

Fluke T6-600 Electrical Tester

Key features

5 reasons the T6 belongs in your toolbelt

  1. Be safer: Measure voltage to 600 V ac through the open fork, without test leads.
  2. Be faster: No need to open covers or remove wire nuts.
  3. Be more efficient: Simultaneously measure voltage and current.
  4. Be everywhere: 17.8 mm open fork is widest in the industry; measure up to 200 A on 4/0 wires (120 mm2).
  5. Go beyond simple detection. Actually measure ac voltage and current values without test leads.

Product Highlights

  • FieldSense technology for ac voltage, current and frequency measurement without making electrical contact to live voltage*
  • See voltage or current display – shows all power supply measurements at a glance for efficient trouble shooting
  • 1 to 600 V ac or dc (T6-600)
  • 0 to 200 A ac
  • True-rms voltage and current
  • Resistance 1 Ω to 2000 Ω
  • Works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
  • HOLD button temporarily freezes the reading for easy viewing
  • Easy to read display with backlight
  • Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient operation
  • Standard two-year warranty; extendable to 4 years through product registration within 45 days of purchase+

Tips: FieldSense Technology

Do not hold or touch wire you are testing during a measurement. Use the black probe to make the ground connection if:

  • wearing gloves or insulated footwear
  • standing on an insulated ladder
  • additional ground contact is required for the application

FieldSense measurement looks like this when properly grounded:

Correct Display

  • Display color turns green
  • Display shows a valid measurement >16 V rather than dashes or 0.0
  • shows for measurement ≥30 V

* Voltage measurement requires capacitive path to ground, provided through user in most applications. Ground connection via test lead may be required in some situations.
+ Register product online within 45 days of purchase to extend warranty to four years. See http://a.fluke.com/registration for details. Two-year additional warranty offer may be discontinued without notice

 

Specifications: Fluke T6-600 Electrical Tester

Measurement Specifications
FunctionRequires test leadsRangeResolutionAccuracy[1]
FieldSense
ac voltage true-rms
No600 V1 V±(3% + 3 counts) 45 Hz - 66 Hz[2] [3]
FieldSense
ac current true-rms
No200.0 A0.1 A±(3% + 3 counts) 45 Hz - 66 Hz
FieldSense
frequency (Hz)
No 1 Hz±(1% + 2 counts)[3]
Volts ac true-rmsYes600 V1 V±(1.5% + 2 counts) 45 Hz - 66 Hz
Volts dcYes600 V1 V±(1% + 2 counts)
ResistanceYes2000 Ω1 Ω±(1% + 2 counts)
Safety 600 V CAT III

Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.

Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.

Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

General Specifications
Calibration1-year calibration cycle
Dimensions61.1 x 259.3 x 43.8 mm
Jaw opening17.8 mm
Weight0.35 kg (0.78 lb)
TemperatureOperating-10 °C to +50 °C (14 °F to 122 °F)
Storage-30 °C to +60 °C (-22 °F to +140 °F)
AltitudeOperating2,000 m (6,562 feet)
Storage10,000 m (32,808 feet)
Relative Humidity0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F)
SafetyIEC/EN 61010-1: Pollution Degree 2
Electromagnetic EnvironmentIEC/EN 61326-1: Portable

Specifications: Fluke T6-600 Electrical Tester

Measurement Specifications
FunctionRequires test leadsRangeResolutionAccuracy[1]
FieldSense
ac voltage true-rms
No600 V1 V±(3% + 3 counts) 45 Hz - 66 Hz[2] [3]
FieldSense
ac current true-rms
No200.0 A0.1 A±(3% + 3 counts) 45 Hz - 66 Hz
FieldSense
frequency (Hz)
No 1 Hz±(1% + 2 counts)[3]
Volts ac true-rmsYes600 V1 V±(1.5% + 2 counts) 45 Hz - 66 Hz
Volts dcYes600 V1 V±(1% + 2 counts)
ResistanceYes2000 Ω1 Ω±(1% + 2 counts)
Safety 600 V CAT III

Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.

Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.

Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

General Specifications
Calibration1-year calibration cycle
Dimensions61.1 x 259.3 x 43.8 mm
Jaw opening17.8 mm
Weight0.35 kg (0.78 lb)
TemperatureOperating-10 °C to +50 °C (14 °F to 122 °F)
Storage-30 °C to +60 °C (-22 °F to +140 °F)
AltitudeOperating2,000 m (6,562 feet)
Storage10,000 m (32,808 feet)
Relative Humidity0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F)
SafetyIEC/EN 61010-1: Pollution Degree 2
Electromagnetic EnvironmentIEC/EN 61326-1: Portable

Top pick accessories

  • Fluke TPAK ToolPak™ Magnetic Meter Hanger - 1

    Fluke TPAK ToolPak™ Magnetic Meter Hanger

Related products

  • Fluke PRV240FS Proving Unit - 1Fluke PRV240FS Proving Unit

    Portable, pocket-sized and battery-powered, the Fluke PRV240FS is the easiest and safest method to verify that your T6 electrical tester is operating properly before you conduct any live tests.

Clamp Meter

Untuk keterangan lebih lanjut, silahkan download PDF ini :