sql

Ground Resistance Tester Kit 300ft with Probes AEMC 6471 Kit-300ft

Rp. 100
Update Terakhir
16 Mar 2023
Pembelian Min
1 Unit
Kategori
AEMC

Spesifikasi Ground Resistance Tester Kit 300ft with Probes AEMC 6471 Kit-300ft

AEMC 6471 Kit-300ft - Ground Resistance Tester Kit 300ft with Probes

Catalog 2135.50

Ground Resistance Tester Model 6471 Kit-300ft w/Probes (Kit Catalog #2135.50) (Cat #2135.49 & Cat. #2135.36)

4-Point Earth Resistance Measurement

Range (Auto-Ranging) 0.01Ω to 99.99kΩ

Resolution 0.001 to 10Ω

Accuracy ±(2% Reading +1ct)

Test Voltage 16 or 32V; 41 to 513Hz

Test Current Up to 250mA

Selective 4-Pole (with optional probes MN82 or SR182)

Same characteristics as with 4-point earth resistance measurement

3-Point Earth Resistance Measurement

Range (Auto-Ranging) 0.09Ω to 99.9kΩ

Resolution 0.01 to 100Ω

Accuracy ±(2% Reading +1ct)

Test Voltage 16 or 32V; 41 to 513Hz 

Test Current Up to 250mA

Soil Resistivity 4-Point Measurement

Test method Wenner or Schlumberger selectable with automatic calculation

Range (Auto-Ranging) 0.01Ω to 99.9kΩ; ρ max: 999kΩm

Resolution 0.01 to 100Ω

Accuracy (Typical) ±(2% Reading +1ct)

Test Voltage 16 or 32V; 41 to 128Hz selectable

2 Clamp Ground Measurement (with optional probes MN82 or SR182)

Range (Auto-Ranging) 0.1 to 500Ω

Resolution 0.01 to 1Ω

Measurement Frequency Auto: 1611Hz; Manual: 128Hz-1367Hz-1611Hz-1758Hz

DC Resistance Measurement (Bond Testing)

2-Pole (with lead resistance compensation) or 4-Pole (Kelvin sensing)

Range (Auto-Ranging) 2-pole: 0.12Ω to 99.9kΩ

4-pole: 0.020Ω to 99.99kΩ

Resolution 2 -pole: 0.01 to 100Ω

4-pole: 0.001 to 10Ω

Accuracy (Typical) ±(2% Reading +2ct)

Test Voltage 16V DC; (+, - or auto polarity)

Test Current Up to 250mA

Current Measurement (with optional probes MN82 or SR182)

Range 0.01mA to 40A, 16 to 400Hz

Accuracy (Typical) ±(3% Reading +2ct) typical

External Voltage Measurement

Range 0.1 to 65V AC/DC – DC, 15 to 440Hz

Accuracy ±(2% Reading +1ct)

General Features

Memory 512 measurements (64KB)

Communication USB 2.0 optically isolated, DataView software included

Power Source 9.6V rechargeable battery pack with external 110/220V charger

Battery Life 1500 tests typical in automatic mode

Dimensions 10.7 x 9.80 x 5.12” (272 x 248 x 130mm)

Weight 7lbs (3.2kg) with battery

Case UL V0 Polypropylene

Operating Temperature 32° to +113°F (0° to +45°C)

Storage Temperature -40° to 158°F (-40° to +70°C)

Relative Humidity Up to 90%

Ingress Protection (IP) IP 53 with cover closed

EMC EN 61326-1

Safety Compliance IEC 61010-1, EN 61557, 50V CAT IV, Pollution Degree 2

Tech Specs

Ground Testers/3 Pole / 4 Pole Ground Testers Template

Type 3 Pole, 4 Pole

Display (3 Pole Testers) Digital

Ground Resistance Range 100 K Ohms

Operating Frequency 5 kHz (5000 Hz)

Accuracy +/-@% of Reading +1ct@128Hz

Measuring Current 250 mA

Measuring Voltage 32 V

Measuring Frequency 513 Hz

Soil Resistivity Yes

Stakeless Capability Yes

Power Supply Line Powered

CAT Rating IV

Optional Ground Kit Included No

Auto Ranging Yes

Earth Tester